5 anti-short-cycle (asc), 6 temperature sensors, 7 diagnostics – LAARS NeoTherm NTV (Sizes 150–850 MBTU/h) - Install and Operating Manual User Manual

Page 63: 8 error codes

Advertising
background image

Page 59

N

eo

T

herm

Boilers and Water heaters

11.5 Anti-Short-Cycle (ASC)

Because the NeoTherm unit is a modulating boiler, and its

input will decrease when there is a reduction in the heating

load, short cycling is greatly reduced. If the heating load

drops below the minimum input of the boiler for an extended

period, the boiler will have a tendency to short cycle. This can

be a symptom of improper control strategy or setpoints, or a

load distribution problem. The controller in the NeoTherm

unit includes an anti-short cycle (ASC) function. The timer

for the ASC can be set to delay the boiler start for a specified

time after a call for heat is completed.

11.6 Temperature Sensors

High Limit Sensor -
The control uses a dual thermistor sensor to monitor the

Neotherm’s maximum temperature. The high limit sensor

is installed in the outlet water. A dual thermistor sensor is

used, so that the two temperatures can be monitored and

compared to confirm accuracy. The control will automatically

reduce the firing of the NeoTherm to prevent the high limit

from tripping. The high limit setpoint is factory set at 195°.

However, if desired you can set a lower limit using the

Adjustable High Limit function available from the Quick

Start menu.

Outlet Water Temperature -
The outlet water temperature is sensed by a dual thermistor

sensor, and is limit-rated. The control compares the two

temperature readings to determine accuracy. The outlet

sensor is used as the primary control point for high limit,

temperature operation, and modulation.

Inlet Water Temperature -
The inlet water temperature uses a single thermistor sensor.

The heat exchanger temperature rise (delta T) is calculated

using the inputs from the outlet and inlet sensor temperatures.

Stack Limit -
The stack temperature is sensed by a dual thermistor

sensor, and is limit-rated. The control compares both of the

temperature readings to determine accuracy. The stack sensor

is used as a limiting feature to avoid excessive temperatures

in the vent.

11.7 Diagnostics

Use the Diagnostics to check the status of the sensors and the

digital inputs and outputs. The system also records a history

of lockouts and alarms.

Analog Sensors -
You can use this display to check on operating temperatures,

fan speed, firing rate, etc. (The word “analog” refers to values

that can change continuously between zero and a higher

value.) The values shown here are “Read Only” – you can’t

change them from this display.

Digital Input/Output -
This display shows whether different functions, inputs and

outputs are either on or off. The functions listed here include

pumps, valves, alarms, etc. The values shown here are “Read

Only” – you can’t change them from this display.

History -
The system records the most recent lockouts or alerts. (If

there is a current lockout or alert, a note about this will also
appear at the bottom of the Home screen.)
• A “lockout” is a condition that will prevent the unit from

starting or running.

• An “alert” indicates a condition that is not normal. If it

continues, the control system might move to a “lockout,” or

the problem might be corrected.

11.8 Error Codes

See Appendix B.

Advertising
This manual is related to the following products: