Burner service, diagrams – LAARS NeoTherm NTV (Sizes 150–850 MBTU/h) - Install and Operating Manual User Manual

Page 59

Advertising
background image

Page 55

N

eo

T

herm

Boilers and Water heaters

the control. If control replacement is required, turn off all

power to the appliance and shut off all manual gas valves

to the appliance. Remove the front door to the appliance

and the plastic bezel and the control panel. Remove all

wire connections from the control board. The control board

connections are keyed to only allow connection in the proper

location, but proper handling techniques should be used to

avoid damage to the wiring or connectors. To remove the

control, push in on the two tabs on the left side of the board

to unlatch the clips from the control panel. Rotate the control

around the fastening points on the right side of the control

to remove the hooks from the control panel. To replace the

control, repeat the steps listed above in the reverse orders

making sure to connect all wires in the proper locations. Place

the appliance in operation following the steps outlined in

Section 9.

Ignitor Assembly
The ignitor assembly is a two rod system that consists of a

ground rod and a spark rod (See Figure 47). To remove the

ignitor assembly, shut off the 120 Volt power supply to the

appliance. Turn off all manual gas valves connecting the

appliance to the main gas supply line. Remove the front door

of the boiler to gain access to the ignitor assembly. Remove

the two wires connected to the assembly. Then remove the

two bolts connecting the ignitor assembly to the burner door.

If the old ignitor assembly is determined to be defective,

install a new ignitor assembly (check that the spark gap is

3/16”). Replace the gasket if necessary.

Flame Sensor
The flame sensor is a single rod system. To replace the flame

sensor electrode, shut off the 120 Volt power supply to the

boiler. Turn off all manual gas valves connecting the boiler

to the main gas supply line. Remove the front door of the

boiler to gain access to the flame sensor electrode. Remove

the flame sensor wire from the electrode. Remove the two

bolts fastening the electrode to the burner doors. Remove

and replace the old flame sensor gasket. If the old electrode

is determined to be defective, install a new flame sensor

electrode in the reverse order.

Caution

The ignitor and sensor may be hot, and can cause

burns or injury.

Figure 47 - Burner Service

NOTES:

SPARK IGNITOR

1.

GIANNONI #gm10-35-108-01

1.08

.18

W20131

3.1

3/16”

Ignitor Assembly

Advertising
This manual is related to the following products: