Dhw piping, -more, Boilers and water heaters – LAARS NeoTherm NTV (Sizes 150–850 MBTU/h) - Install and Operating Manual User Manual

Page 33

Advertising
background image

Page 29

N

eo

T

herm

Boilers and Water heaters

Figure 24 - DHW Piping, Two Heaters, One Vertical Tank

Figure 25 - DHW Piping, Two Heaters, Two Vertical Tanks

NOTES:

1. Optional CWMU & Recirc. line location.

2. Locate NTV DHW sensor or remote aquastat

well in lower 1/3 of tank.

3. Back flow preventer may be required - check

local codes.

4. Thermal expansion tank may be required -

check local codes.

5. Factory mounted pumps are sized for a max

pipe length of 30’ total, 6-90° elbows, full pipe size.

6.

Caution: Pump sizing must be based on

water hardness at job site.

WARNING: This drawing shows

suggested piping configuration and

valving. Check with local codes and

ordinances for additional requirements.

NOTES:

1. Optional CWMU & Recirc.

line location.

2. Locate NTV DHW sensor

or remote aquastat well

in lower 1/3 of tank.

3. Back flow preventer may be

required - check local codes.

4. Thermal expansion tank may be

required - check local codes.

5. Factory mounted pumps are sized

for a max pipe length of 30’ total,

6-90° elbows, full pipe size.

6.

Caution: Pump sizing must

be based on water

hardness at job site.

WARNING: This drawing shows

suggested piping configuration and

valving. Check with local codes and

ordinances for additional requirements.