Appendix b - error messages – LAARS NeoTherm NTV (Sizes 150–850 MBTU/h) - Install and Operating Manual User Manual

Page 80

Advertising
background image

Page 76

LAARS Heating Systems

Appendix B -

ERROR MESSAGES

This table includes a listing of the faults that might be generated by the controller, and displayed on the Operator

Interface. Some of these can be corrected by an installer changing a parameter, while other conditions are more

complicated, and will require a service technician.
The first column lists the code number that will appear at the beginning of the Lockout or Hold message. The second

column lists a short description of the condition. The third column shows whether the condition will cause a Hold, or

Lockout, or both. The fourth column lists some suggestions for corrective action.

Code Description

L or H Procedure

1

Unconfigured safety data

L

1. New device, complete device configuration and safety verification.
2. If fault repeats, replace module.

2.

Waiting for safety
data verification

L

1. Device in Configuration mode and safety parameters need

verification and a device needs reset to complete verification.
2. Configuration ended without verification, re enter configuration,

verify safety.
parameters and reset device to complete verification.
3. If fault repeats, replace module.

3

Internal fault:
Hardware fault

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

4

Internal fault:
Safety Relay key feedback error

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

5

Internal fault:
Unstable power (DC) output

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

6

Internal fault:
Invalid processor clock

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

7

Internal fault:
Safety relay drive error

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

8

Internal fault:
Zero crossing not detected

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

9

Internal fault:
Flame bias out of range

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

10

Internal fault:
Invalid burner control state

L

Internal fault
1. Reset module
2. If fault repeats, replace module.

11

Internal fault:
Invalid burner control state flag

L

Internal fault
1. Reset module
2. If fault repeats, replace module.