LAARS NeoTherm NTV (Sizes 150–850 MBTU/h) - Install and Operating Manual User Manual

Page 85

Advertising
background image

Page 81

N

eo

T

herm

Boilers and Water heaters

108

Flame lost in run

L

1. Check main valve wiring and operation - correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, flame detector, flame detector

siting or flame rod position.
5. If steps 1 through 4 are correct and the fault persists, replace the

module.

109

Ignition failed

L

1. Check the main valve wiring and operation - correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, flame detector, flame detector

siting or flame rod position.
5. If steps 1 through 4 are correct and the fault persists, replace the

module.

110

Ignition failure occurred

H

Hold time of recycle and hold option. Will not be a lockout fault. Hold

only. Internal hardware test. Not a lockout.

111

Flame current lower than weak

threshold

H

Hold time of recycle and hold option. Will not be a lockout fault. Hold

only. Internal hardware test. Not a lockout.

113

Flame circuit timeout

L

Flame sensed during initiate or off cycle. Produces a Hold for 240

seconds. If still present after 240 seconds, system will lockout.

122

Lightoff rate proving failed

L

1. Check wiring and correct any potential wiring errors.
2. Check VFD’s (Variable-speed Fan Drive) ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.

123

Purge rate proving failed

L

1. Check wiring and correct any potential wiring errors.
2. Check VFD’s (Variable-speed Fan Drive) ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.

128

Fan speed failed during prepurge H or L 1. Check wiring and correct any potential wiring errors.

2. Check the VFDs (Variable-speed Fan Drive) ability to change

speeds.
3. Change the VFD
4. If the fault persists, replace the module.

129

Fan speed failed during

preignition

H or L 1. Check wiring and correct any potential wiring errors.

2. Check the VFDs (Variable-speed Fan Drive) ability to change

speeds.
3. Change the VFD
4. If the fault persists, replace the module.

130

Fan speed failed during ignition

H or L 1. Check wiring and correct any potential wiring errors.

2. Check the VFDs (Variable-speed Fan Drive) ability to change

speeds.
3. Change the VFD
4. If the fault persists, replace the module.

131

Fan movement detected during

standby

H

1. Check wiring and correct any potential wiring errors.
2. Check the VFDs (Variable-speed Fan Drive) ability to change

speeds.
3. Change the VFD
4. If the fault persists, replace the module.

Code Description

L or H Procedure

Advertising
This manual is related to the following products: