Dunkirk Q95M-200 Modulating Condensing Boiler User Manual

Page 11

Advertising
background image

11

Pressure Guidelines

Fan Speed

Minimum RPM

Maximum RPM

Fuel

Natural Gas

LP

Natural Gas

LP

Gas Line Inlet

Pressure

N/A

N/A

At least 4” WC

At least 10” WC

Differential Pres-

sure

0.3” WC

2.0” WC

Note: Differential pressure values listed for comparison only. These values will change with vent length

and altitude of installation.

Combustion Guidelines

Outside

Natural Gas

LP Gas

Temperature

*%CO

2

*%O

2

CO

*%CO2

*%O

2

CO

70°F and up

9.6% to

10%

3.9% to

3.2%

Less than

80 PPM

11.1% to

11.5%

4.1% to

3.4%

Less than

80 PPM

21°C and up
30°F to 70°F

9.3% to

9.6%

4.4% to

3.9%

Less than

80 PPM

10.8% to

11.1%

4.5% to

4.1%

Less than

80 PPM

-1°C to 21°C
30°F and below

9.0% to

9.3%

5.0% to

4.4%

Less than

80 PPM

10.5% to

10.8%

4.9% to

4.5%

Less than

80 PPM

-1°C and below

* Percent CO

2

values may exceed those listed and percent O

2

values may be less than those listed in order

to achieve nominal input rate of boiler.
Flame Signal Guidelines

Fan Speed

Minimum RPM

Maximum RPM

Flame Signal

Greater than 3.0 VDC

Greater than 3.0 VDC

6 - CHECKOUT PROCEDURES AND ADJUSTMENTS