4

3.

DHW heating: Target temperature is determined by

adding Parameter 1 to Parameter 33 (default 150°F

and 30°F). Do not change Parameter 1 from factory

default setting of 150°F unless application is specially

engineered for other temperature. DHW heating default

setting is 180°F.

4.

High limit operation: If outlet water temperature

exceeds target temperature (or 180°F, whichever is

lower), high limit action occurs. Control module shuts

burner off showing “b 9” followed by “26” on display.

5.

DHW operation (if used): Boiler is factory set to

change target outlet water temperature to 180°F on

call for heat from DHW aquastat.

6.

Additional Thermal Overrun Protection: High

limit operation shuts down burner when outlet

water temperature exceeds target temperature.

Adverse conditions could cause water temperature

to rise too quickly and overshoot this temperature.

Control’s advanced technology provides protection in

event of thermal overrun. Using its electronics, control

provides two additional levels of overrun protection:

• Level 1: Indication occurs if supply water temperature

reached 183°F. Control displays soft lockout code (“b

9” followed by “18” if on supply or “19” if on return).

Control will not operate burner again until water

temperature dropped 9°F below target temperature.

• Level 2: Lockout occurs if supply water temperature

reaches 200°F or if return water reaches 193°F. Control

will enter hard lockout and display error code (“E”

followed by “18” if on supply or “19” if on return).

NOTICE

Hard lockout requires manually pressing display panel

reset button to restart operation. Service technician

must troubleshoot cause of problem and correct it

before placing boiler back in operation.

Low Water/Low Flow Protection
1.

Boiler is factory equipped with manual reset probe type

low water cutoff.

2.

Boiler control uses temperatures sensed at both supply

and return areas of heat exchanger. If flow rate is

too low (temperature difference too high) or either

temperature is too high, control shuts boiler down.

Ensures boiler shutdown in event of low water or low

flow conditions.

Freeze Protection

Do not install boiler in room likely to freeze.

Following boiler control feature provides some protection for boiler

only, not for the system.

Boiler is controlled by microprocessor electronic control that

senses:

• Outlet water temperature,

• Return water temperature,

• Outdoor temperature (when factory supplied, field

installed outdoor sensor is installed).

Information sensed plus input from external limit and

operating controls is used to regulate boiler on/off

operation and will modulate boiler firing rate to more

closely match output to demand.

Electrical Specifications

Boilers require 120 VAC/60 HZ power supply and are not

polarity sensitive.

CONTROL SPECIFICATIONS

Supply voltage

120 Vac/60 hz

Electrical demand

10 VA

Pre-purge timing

10 Seconds

Post-purge timing

15 Seconds

Min. off time, space heating

10.2 Seconds

Pump on after space htg.

0 Minutes

Min. off time, DHW

10.2 Seconds

Pump on after DHW

30.6 Seconds

Line voltage fuse, F1

5 Amp fast-blow

Low voltage fuse, F3

4 Amp slow-blow

Boiler Circulator

• Circulator has sufficient head to handle boiler pressure

drop plus reasonable pressure drop in connecting

piping. See the Installation, Operation and Maintenance

Manual for piping information.

• Boiler control’s internal relay contact is suitable for

handling only the boiler circulator provided.

• Do not wire additional pumps in parallel with boiler

circulator.

• To operate system circulator when boiler circulator is

running, see “Electrical Wiring” section in Installation,

Operation and Maintenance Manual for wiring required.

Boiler Temperature Regulation

Operating temperature (target): Control senses outlet water

temperature and regulates boiler firing rate to achieve

target temperature set by installer using Parameter 4.
Temperature can be set between 120°F and 194°F.

1.

Space heating: Target temperature is fixed (equal

to Parameter 4) when outdoor reset is not installed

or calculated as described under “Outdoor Reset

Operation” page 5, when outdoor sensor is connected.

2.

Exception: See explanation of “Supply Temperature

Boost” page 5.

3 - OPERATING INFORMATION