25

HARD LOCKOUT MODE

Boiler in hard lockout (requires manual RESET)

Display flashes first digit E

E

and last two digits (lockout code) (see below)

xx

Code

Reason for hard lockout

Code

Reason for hard lockout

00

Flame detected on start-up

18

Supply water temperature higher than 200°F

02

Ignition failed after 5 retries

19

Return water temperature higher than 190°F

03

Gas valve disconnected

25

Outlet temperature increased too fast

04

Power lost after lockout

28

No signal from blower; blower not running or defective blower motor

05

Internal control failure

29

Blower signal not “0” when it should be

06

Internal control failure

30

Max difference (b30) was too large for 20 successive times. Non

adjustable default max delta set to 100°F.

07

Internal control failure

31

Outlet temperature sensor short circuit

11

Internal control error

32

Return temperature sensor short circuit

12

Casting temperature switch open

36

Outlet temperature sensor open circuit

13

Internal control failure

37

Return temperature sensor open circuit

14

Internal control failure

44

Internal control failure

15

Internal control failure

60

Internal error reading parameters

16

Internal control failure

61

Air flow circuit failure

17

Internal control failure

65

Not enough blower driving force

10 - USER INTERFACE QUICK REFERENCE