Startup
1.

Start boiler after completing all instructions in

Installation, Operation and Maintenance Manual.

2.

Start boiler by turning thermostat up to call for heat.

3.

Once boiler has started and is operating, continue

startup procedure by performing all following steps to

set and verify operation of controls.

Set Space Heating Operation
1.

Verify Space Heating Mode
A. Press “Mode” button until display shows [PARA].

This is parameter mode.

B. Press “Step” button until first digit of display shows

“3.”

C. Last digit must show “1.” If any other number

displays, press “+” button until “1” shows in right-

hand digit, then press “Store” button to save this

setting.

2.

Set space heating target temperature
A. Press “Step” button until first digit of display

shows “4.” Last three digits show outlet water

temperature setting.

B. Press “+” or “-” buttons to change setting to

desired outlet water temperature. Factory default

setting is 180°F.

• Outdoor sensor installed: Setting is target

temperature for outdoor temperature at or

below factory setting (32°F). At higher outside

temperatures, control module calculates target

temperature.

• When summer/winter switch is used, closing

switch will disable boiler (space heating) circulator

during summer operation.

• Outdoor sensor not installed: Setting is target

temperature at all times.

C. Press “Store” button to save setting.

Check DHW Operation Setup

If control is already in parameter mode , skip step 1 (below)

and proceed to step 2.

1.

Press “Mode” button until display shows [PARA]

(parameter mode).

2.

Press “Step” button until first digit of display shows “2.”

3.

Last digit must show “1.” If another number displays,

press “+” button until “1” shows in right-hand digit,

press “Store” button to save this setting.

4.

Control module turns on DHW circulator when indirect

water heater operating control closes. Control module

shuts off boiler circulator (stops space heating) during

calls for DHW heating.

Verify Operation – Space Heating

Information below presented in brackets “[ ]” represents

actual boiler control panel display with first digit indicating

boiler status and last three digits showing measured boiler

water temperature. (Ex.- [A180] indicates status of “A” and

boiler water temperature of 180°F.)

1.

Turn down DHW aquastat on DHW tank (if used). If

necessary, turn off power and remove one of DHW

aquastat wires to ensure boiler will not receive DHW

heat call.

2.

Turn off power to boiler at service switch.

3.

Wait few seconds, then turn on power to boiler.

• [180] Self-check on power-up for a few seconds.
• [0180] No call for heat.

4.

Raise room thermostat to call for heat.

• [5180] Blower/boiler circulator on. Blower and boiler

circulator energize and control checks for air flow.

• [1180] Pre-purge. Blower speed will increase to ignition

speed. Blower will run in pre-purge for 10 seconds.

• [2180] Ignition. After pre-purge, control module opens

gas valve and starts ignition spark.

• If burner flame proves within 4.5 seconds, burner

continues to fire. Burner will fire at startup rate for

about 10 seconds to allow flame to stabilize.

• If burner flame does not prove within 4.5 seconds,

control module attempts ignition sequence again.

Flame must prove within 6 attempts or control will

lockout (display will show [E 02]).

• Verify flame failure operation by closing boiler manual

gas cock to prevent gas flow. Open manual gas valve

after testing.

• [3180] Burner on, space heating. Once flame is

proven and stable, burner turns down to low fire for

approximately 2 minutes.

• After this low fire period, burner is allowed to modulate.

Firing rate depends on actual outlet water temperature

versus target temperature.

5.

Allow boiler to bring water temperature to target

temperature.

• [6180] Target temperature reached. Burner shuts

down. Blower runs in post-purge (see below), then

turns off. Boiler circulator continues to run as long as

there is call for heat.

6.

Lower room thermostat to stop call for heat.

NOTICE

Instructions in this manual are based on factory

default parameter settings.

5 - BOILER STARTUP