14

Differential Air Pressure

Differential air pressure switch is a safety device which

prevents boiler from firing if there is an air intake, boiler

heat exchanger or vent blockage.
To check differential air pressure:

1.

Turn off service switch or lower thermostat setting.

2.

Remove vinyl caps from tee.

3.

Install testing lines as shown to inclined manometer

or differential pressure gauge with ability to read

0.01” increments to at least 6.0” w.c.

4.

Turn on service switch and set thermostat to call for

heat.

Boiler Status

Diff. Pressure Switch Contacts

Not Running

0”

3.5”

Closed

0.14”

Open

Running with

Blockage

Greater Than or

Equal To Setpoints

3.5”

Open

0.14”

Closed

Running w/out

Blockage (approx.)

Min. Fire: 0.3”

3.5”

Closed

Max. Fire: 2”

0.14”

Closed

If manometer readings do not correspond with chart

above, check for possible causes:

• Blockage or moisture in suction lines to switch.
• Blockage in air intake or vent pipes.
• Undersized air intake or vent pipes.
• Loose blower wheel on motor shaft.
• Incorrect pressure switch or pressure switch setpoint

When pressure reading is correct and pressure switch

is operating properly, remove testing lines and reinstall

vinyl caps to Tee and 3-way connector.

Checking the Differential Air Pressure

9 - TROUBLESHOOTING

DANGER

Electric shock hazard! Following procedures may

expose you to dangerous line voltage. Use caution

to avoid touching live electrical contacts. All service

must be performed by a trained, experienced service

technician. Failure to follow these instructions WILL

result in death or serious injury

!

CAUTION

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.
• Do not touch any electrical switch; do not use

any phone in your building.

• Immediately call your gas supplier from a

neighbor’s phone. Follow gas supplier’s

instructions.

• If you cannot reach your gas supplier, call the fire

department.

!

WARNING

Fire, Explosion. Shut off gas at a location external

to appliance should overheating occur or gas

supply fail to shut off. Do not turn off or disconnect

electrical supply to pump. Do not use the boiler

if any part of the gas control system has been

underwater.
Only a qualified service technician should inspect

the boiler and replace any part of control system

and any gas control which has been underwater.
Use only your hand to turn gas control knob. Never

use tools. If knob will not turn by hand, don’t try to

repair it.
Failure to follow these instructions could result in

death or serious injury.

!