9 - troubleshooting – Dunkirk Q95M-200 Modulating Condensing Boiler User Manual

Page 16

Advertising
background image

16

Boiler Not Firing And:

Check For:

Step

Corrective Actions:

Control display blank

120 vac at terminals L1 and L2 of line

voltage strip?

1

NO - Check external line switch and fuse or breaker.

2

Determine if red light on line voltage monitor is flashing

indication fault. If there is fault verify input voltage dial

is properly set in accordance with steps in installation

manual. If fault does not clear after ten minutes replace

line monitor.

120 vac on both sides of fuse F1?

1

NO - Turn off power to boiler and replace fuse if

necessary. Inspect boiler interior wiring to determine

cause of fuse opening.

Wiring correct, in good condition, and

securely attached?

1

Correct if needed. Replace any damaged wiring or

components. Replace control module if problem persists.

Display first digit shows

0; last digits show 2 or

3-digit number (boiler

outlet water temp.)

Room thermostat and DHW aquastat

satisfied?

1

YES - Boiler off, no call for heat. Turn up thermostat or

aquastat. Boiler should start.

Thermostat or aquastat calling for heat

but boiler not firing.

1

Check voltage on both sides of low voltage fuse F3. (Turn

OFF external power before removing cover.) If necessary,

replace fuse. Determine reason for fuse failure if possible.

2

Check/set boiler parameters 2 and 3. Make sure space

heat or DHW is turned on. Turn on if necessary.

3

Turn off power to boiler. Temporarily jumper low voltage

terminal strip terminals T1 and T2 or DHW T1 and

DHW T2. Retry. If boiler operates, check CH and DHW

thermostat and wiring. Replace if necessary. Remove

temporary jumper(s).

4

Turn off power to boiler. Check wiring against wiring

diagram; verify all wiring in good condition and secure.

5

Replace wire harnesses and retry.

6

Replace control module.

Display first digit shows number from 1 to 8; last digits show 2 or

3-digit number (boiler outlet water temp.)

1

Boiler in normal operating mode.

Display flashes “9,” then “b.” Last two digits show code number.

1

See User Interface Quick Reference and Soft Lockout

Troubleshooting for more information on soft lockout code.

Display shows U 1.25

continuously

Transformer unplugged or not

functional

1

Plug transformer in.

2

Replace transformer.

F3 24V 4 Amp fuse is not functional

1

Replace fuse.

9 - TROUBLESHOOTING