Dunkirk Q95M-200 Modulating Condensing Boiler User Manual

Page 6

Advertising
background image

6

Boiler Control Design

• Integrated modulating boiler control is designed for

central heating (CH) hot water boilers with modulating

fan and gas-air control.

• Modulation is based upon data relayed to control by

temperature sensors.

• Burner uses direct spark igniter (DSI).

• Modulating boiler control is intended for use in

combination with user interface display unit for both

information and operation.

• Control is designed for installation with conventional on/

off dry contact room thermostat.

• Control is able to provide hot water and outdoor reset

functions.

Main Controller Functions

Central Heat (CH): Control uses sensors on supply water,

return water and outside air to determine heat load of

heating system. Results in boiler supplying just enough

heat to satisfy demand which results in fewer overshoots

and less short cycling than conventional boiler.
Domestic Hot Water (DHW): When used in conjunction

with indirect hot water heater boiler has capability to

provide domestic hot water. An on/off dry contact aquastat

is used to activate call for domestic hot water.
Outdoor Reset: Control senses outside air temperature

using factory supplied, field installed sensor. Controller

detects presence of sensor and reacts according to

parameters programmed into controller.

User Interface Display

User interface display allows installer and home owner to

scroll through control settings and customize boiler to heat

delivery system used in installation location. See “User

Interface Quick Reference” Section 10, page 21 for more

information on using and programming boiler control.

4 - MODULATING CONTROL FEATURES

IMPORTANT:
This boiler is equipped with a feature that saves energy

by reducing the boiler water temperature as the heating

load decreases. This feature is equipped with an override

which is provided primarily to permit the use of an external

energy management system that serves the same function.
This Override Must Not Be Used Unless At Least One Of The

Following Conditions Is True:

• An external energy management system is installed

that reduces the boiler water temperature as the

heating load decreases.

• This boiler is not used for any space heating.
• This boiler is part of a modular or multiple boiler

system having a total input of 300,000 BTU/hr or

greater.