Warning – Dunkirk Q95M-200 Modulating Condensing Boiler User Manual

Page 13

Advertising
background image

13

Troubleshooting Tools

Tools needed for troubleshooting your boiler:

• Voltmeter that can check 120 VAC, 24 VAC, and 12

VDC

• Continuity Tester
• Contact Thermometer
• Inclined Manometer or Pressure Gauge with 0-6.0”

range (0.01” scale) for measuring suction pressures at

pressure switch

• U-Tube Manometer or Differential Pressure Gauge

with 0-14” range (0.1” scale) for measuring inlet and

manifold gas pressures

Initial Service Checks

Prior to troubleshooting:

1.

Verify circuit breaker is ON or fuse is okay at electrical

panel.

2.

Verify service switch is ON.

3.

Verify 120 VAC (minimum 102 VAC to maximum 132

VAC) to boiler.

4.

Verify thermostat is calling for heat and contacts

(including appropriate zone controls) are closed. Check

for 24 VAC between thermostat wire nuts and ground.

5.

Verify all external limit controls are either installed (and

closed) or temporarily jumpered for testing.

6.

Verify gas is ON at gas meter, at all appropriate manual

shutoff valves, and at gas control valve. Gas pressures

should be maximum of 10” w.c. (natural gas) or 14”

w.c. (for LP gas) with no flow (lockup) or with boiler on

and minimum of 5” w.c. with gas flowing (verify during

boiler startup with boiler at high fire).

7.

Verify wire connectors at boiler control and at

originating control are securely plugged in or

connected.

8.

Verify all hoses are securely connected and are not

plugged in or damaged.

8 - SERVICE HINTS

WARNING

Fire, Explosion, Shock Hazard. Revision,

modification, substitution or elimination of factory

equipped, supplied or specified components could

result in death or serious injury.

!

Important Service Information

• If any component does not function properly, make

sure it is correctly installed and wired before replacing

it.

• Static electricity discharge can damage the integrated

modulating boiler control (IMBC). Touch metal surface

to discharge static electricity before touching control.

• Boiler control cannot be repaired. If it malfunctions it

must be replaced.

• Only trained, experienced service technicians should

service boiler control systems.

• After troubleshooting, follow “Detailed Sequence of

Operation” Section 7 page 12, for normal light off

procedure.

• All controls are factory tested,a defective control is

generally least likely cause. If you suspect you have a

defective boiler control, read “Troubleshooting” Section

9 before you replace it.

• It is unlikely that two consecutive controls are

defective. Chances are that either there is nothing

wrong with the control or it is damaged by some other

problem (for example, an electrical short burning out a

transformer).

Advertising