Danger – Dunkirk Q95M-200 Modulating Condensing Boiler User Manual

Page 15

Advertising
background image

15

Control Module Fuses

Check control module fuses before replacing control module

or any major components (blower, etc.) If one of these

fuses is blown, it can prevent control module or other

components from operating.

1.

Turn OFF power to boiler at external line switch.

2.

Remove jacket front panel.

3.

Remove control module cover.

4.

Inspect fuses F1 and F3 (shown below).

5.

Boiler is shipped with four spare fuses attached to

control module cover.

6.

If necessary, replace open fuse (F1 is 115V, 5-amp

fast-blow; F3 is 24V, 4-amp slow-blow).

7.

Install control module cover and jacket top front cover

after fuse inspection.

8.

Restore power to boiler at external line switch and

verify boiler operation after completing boiler service.

Checking Temperature Sensors
1.

Boiler temperature sensors (outdoor, return water, and

supply water) are all resistance-type devices.

2.

Table 1 shows correct resistance value for sensor at

various temperatures.

3.

Use resistance values at 32°F, 60°F, 70°F and 212°F to

measure sensor resistance at known temperatures (ice

point, room temperature and sea level boiling point).

For ice point and boiling point, insert sensor in water

at that temperature. Use ohm meter to read resistance

value.

4.

To verify control module is correctly sensing

temperature, use a resistance decade box. Connect

decade box temporarily in place of sensor. Use control

module “Information” mode to read temperature.

9 - TROUBLESHOOTING

DANGER

Electric shock hazard! Disconnect power before

servicing. All service must be performed by a

trained, experienced service technician. Never

jumper (bypass) any device except for momentary

testing as outlined on the following pages of this

manual. Failure to follow these instructions WILL

result in death or serious injury

!

F1 and F3 Fuses

Temp

°F

Sensor Ohms

Temp

°F

Sensor Ohms

Min

Max

Min

Max

32

34,265

37,871

130

3,698

4,088

40

27,834

30,764

140

3,043

3,364

50

21,630

23,907

150

2,517

2,782

60

16,944

18,727

160

2,091

2,311

70

13,372

14,780

170

1,744

1,928

80

10,629

11,747

180

1,461

1,615

90

8,504

9,399

190

1,229

1,359

100

6,847

7,568

200

1,038

1,147

110

5,545

6,129

210

880

972

120

4,517

4,992

212

851

941

Table 1 - Sensor Resistance Values at Various

Temperatures