LINK Systems System 1100 Tonnage Monitor User Manual

Page 104

Advertising
background image

10-1

10.1 Error Listing

System 1100 errors are indicated by the STOP CIRCUIT indicator
light flashing. The codes and descriptions for any active errors
can be displayed using the ERRORS option in the main menu (section
2.7).

Errors are cleared by pressing the CLEAR key. Depending on the
System 1100 configuration, the keyswitch may have to be in the PROG
position to clear errors.

The following is a listing of error codes generated by the System
1100 Tonnage Monitor, software version 1.0, and suggested action
for correction of the errors.

Error No.

Message / Action

001

Channel 1 will not zero.

002

Channel 2 will not zero.

003

Channel 3 will not zero.

004

Channel 4 will not zero.

Error codes 001, 002, 003, and 004 indicate that the
output of the channel card identified by the error
code fails to zero when no load is present. These
error codes are caused by a fault in the strain link
that is connected as an input to the channel card,
or in the wiring from the strain link to the channel
card input terminals.

1)

Press the CLEAR key to see if the error code
clears (depending on the System 1100
configuration, you may have to be in PROG mode
to clear errors).

2)

If the error code does not clear after pushing
the CLEAR key, turn off the power to the System
1100 and open the front door of the enclosure.
Check the connections to the strain link that is
input to the channel indicated by the error
code. If all connections are proper proceed to
step 3.

3)

Open the door of the System 1100 enclosure and
unplug the strain link in error and the adjacent

Section 10. Error Codes