ERROR CODES

___________________________________________________________________

Error No.

Message / Action

10-3

2)

If running at speeds greater than 500 SPM a
zeroing cam switch should be installed.

031

Supply Voltage too low.

When the operator attempts to change information
stored in the non-volatile memory of the System 1100
the power supply voltage is first checked for the
proper level. If the proper level does not exist,
the System 1100 will not change data in the non-
volatile memory and this error will result.

1)

For self-contained System 1100 Tonnage Monitors
open the front door of the enclosure and
visually inspect the four power supply indicator
lights for uniform and proper brightness.

For remote display System 1100 Tonnage Monitors
open the back of the Operator Interface Terminal
and visually inspect the two power supply
indicator lights for uniform and proper
brightness.

2)

Check the 110VAC power line to the System 1100
for proper level.

032

Internal Error. Call Factory.

1)

Notify Link Systems of this error.

033

Internal Error. Call Factory.

1)

Notify Link Systems of this error.

034

Internal Error. Call Factory.

1)

Notify Link Systems of this error.