11. Programming example of the Week Program Editor

11.1 Desired time function

From Monday to Friday the chamber shall maintain a temperature of +20 °C / 68°F, and during the week-

end (Saturday and Sunday) a temperature of +5 °C / 41°F.
This program shall automatically run during the whole year, i.e. it shall be programmed just once.

11.2 Proceeding overview

1. Settings in the user level (see chap.

10

)

Setting the safety controller to “Limit” and 3 °C above the maximum temperature value of the

program
The temperature set-point of the safety controller (over temperature protection class 3.1) is displayed

and can be changed. You can enter an absolute value in case of setting “limit”, or a relative value in

case of setting “Offset”. Select setting “Limit” and enter a value by 3 °C above the maximum value (i.e.,

23 °C / 73.4°F).

Activating the week program timer

Checking and, if necessary, setting the real time clock


2. Entering the set-points for the week program in “Fixed value entry mode” (see chap. 6)

Set-points for the example program:
SP 1 (night / weekend) = 5 °C / 41 °F
SP 2 (day / week) = 20 °C / 68 °F

3. Entering the time program to the week program editor (see chap. 7)

Program table for the example program:

Day of the week

Time

Channel 1 (temperature)

hh:mm

AM

PM

ON (SP2)

OFF (SP1)

Monday

S1

06:00

ON

Friday

S1

20:00

OFF

Make sure that no other shift points have been preprogrammed. If so, they must be deleted:
Set the time of the respective shift point to “