Connections – CIRCUTOR CEM-C30 series User Manual

Page 11

Advertising
background image

3.5.- CONNECTIONS

The

CEM-C30 has terminal covers to cover the top of the terminal box and the fixing screws

(

Figure 3

).

Figure 3: Terminal covers of the CEM-C30�

The fixing screws are of the mixed type, allowing the use of PZ2 and flat head screwdrivers.

Table 4:CEM-C30 connections�

Connections

Measurement terminals ( 1, 2, 3, 4, 5, 6, 7, 8, 9, 11)
Maximum cable cross-section

16 mm

2

( 10 mm

2

with end sleeve ) 1.2 Nm

Screwdrivers head

PZ2

Impulse output terminals ( 21, 22 ) and Power supply ( 13, 14)
Maximum cable cross-section

1.5 mm

2

( 1.5 mm

2

with end sleeve ) 0.6 Nm

Screwdrivers head

flat head ( 3 x 0.5 mm)

Once connected, the unit can be protected with two connection seals (

Figure 4

).

Figure 4: Seal of the CEM-C30�

11

Instruction Manual

CEM-C30

Advertising
This manual is related to the following products: