5�- TECHNICAL FEATURES

Power supply

Mode

Auxiliary

Rated voltage

230 V ~

Tolerance

± 20 %

Frequency

50...60Hz

Consumption

< 2 W

< 10VA (In, Vref (without auxiliary services))

Voltage Measurement

Connection

Three-phase

Reference voltages

(according to version)

V

L

3x57/100 ... 3x230/400V ~

3x57/100 V ~

M

N

Q

3x63.5/110 V ~

3x127/220 V ~ 3x230/400 V ~

Frequency

(according to version)

A

B

C

50 Hz

60 Hz

50/60 Hz

Self-consumption of the voltage

circuit

< 2 W

< 10VA (In, Vref (without auxiliary services))

Current measurement (according to version)

T6 T5

Current (Ib / Iref)

5 A

5 A

Maximum current (Imax)

6 A

10 A

Start-up current

0.04% of Itr

0.04% of Itr

Self-consumption of the current circuit

0.3 VA @ 10 A

0.3 VA @ 10 A

Itr

0.250 A

0.250 A

Ist

0.010 A

0.010 A

Imin

0.050 A

0.050 A

Maximum overcurrent time

( 20xImax) ( according to EN-50470-3)

500 ms

500 ms

Accuracy

Active Energy

CEM-C30 MID

CEM-C30

Class B (EN 50470)

Class 1 (IEC 62053-21)

Reactive Energy

Class 2.0 (IEC 62053-23)

Insulation

AC voltage

4kV RMS 50Hz during 1 minute

Overimpulse

1�2/50ms 0R source impedance

6 kV at 60º and 240º, with positive and negative polarization

Calculation and processing

Microprocessor

ARM

AD converter

16-bit

Impulse output

Type

Optocoupler

Operation

Emission of impulses proportional to the energy

Electrical features

Max. 24V 50mA

Impulse ON/OFF time

40 ms