Configuration, Filter, Start-up – CIRCUTOR AFQ Series User Manual

Page 27: Configuration of the current transformer

Advertising
background image

AFQ-4W

Instruction Manual 27

3.8.- FILTER START-UP

Finally, start-up the AFQ-4W. To consult all of the configuration parameters in

detail, see

4.3.- CONFIGURATION

of this manual.

Before starting up the AFQ-4W, carefully follow the steps given in

Configuration 3.8.1 and Verification of the unit 3.8.2.

3.8.1- CONFIGURATION

3.8.1.1.- CONFIGURATION OF THE CURRENT TRANSFORMER

Access the parameter configuration screen by pressing SETUP and select the

PARAMETERS option (

Figure 22

):

Figure 22: Configuration of the transformer ratio and the number of modules in parallel.

Configure the TRANSFORMER RATIO parameter with the ratio between the

primary and secondary of the load current measurement transformer.

The AFQ-4W admits the following transformation ratios: 5/5, 10/5, 15/5, 20/5,

25/5, 30/5, 40/5, 50/5, 60/5, 75/5, 100/5, 125/5, 150/5, 200/5, 250/5, 300/5,

400/5, 500/5, 600/5, 700/5, 750/5, 800/5, 1000/5, 1200/5, 1500/5, 1600/5,

2000/5, 2500/5, 3000/5, 4000/5 and 5000/5.

If the transformer ratio is not that of the transformer installed, the

AFQ-4W will not work properly.

Advertising