3.8.2.2.- VERIFICATION OF THE ACTIVE AND REACTIVE POWER

The load power screen (

Figure 25

) can be accessed from the home screen by

pressing VIEW:

Figure 25: Verify active and reactive power and load power factor readings.

 Make sure the active power measurement of the load equals the power

levels of the installation.

 Make sure the reactive power measurement of the mains equals the

reactive power levels of the installation.

 Check the power factor in the three phases. If there are phases with very

high reactive power and very low active power levels, this might indicate

an error in the phase order. In this case, check the connections of the

three-phase mains power supply cables with neutral and the load current

reading cables, as described in sections 3.5.1 and 3.5.2.