Afq-4w instruction manual 99 – CIRCUTOR AFQ Series User Manual

Page 99

Advertising
background image

AFQ-4W

Instruction Manual 99

Name

Type

Function

Address (Hexadecimal)

Minimum load current

Word

R/W

0015

Response

Description

Response in Amps without decimals.

Minimum load current to start the

AFQ-4W

Name

Type Function

Address (Hexadecimal)

AFQ range Word

R/W

0016

Response

Description

25 / 50 / 100 / 150 / 200

Unit range

.

WARNING: DO NOT MODIFY

Name

Type

Function

Address (Hexadecimal)

Configuration code

Word

R/W

0017

Response

14: Complete configuration
25: Enter AFQ-4W configuration

Name

Type

Function

Address (Hexadecimal)

AFQ software version

Word

R

0018

Response

Description

Response format X.XX

AFQ software version

Name

Type

Function

Address (Hexadecimal)

Control algorithm

Word

R/W

0019

Response

Description

1: Frequency mode
2: Temporary mode

Control algorithm selection

Name

Type

Function

Address (Hexadecimal)

Parallel AFQ number

Word

R/W

001A

Bit

Response

Description

0
1
2

No. of AFQ-4W 25A

Numbering from 0 to 7

Number of AFQ-4W installed in parallel.

The value is coded in 16 bits.

Note The consulted unit counts as 1u.,

so the minimum value will be 001 for the

consulted range.

3
4
5

No. of AFQ-4W 50A

Numbering from 0 to 7

6
7
8

No. of AFQ-4W 100A

Numbering from 0 to 7

9

A
B

No. of AFQ-4W 150A

Numbering from 0 to 7

C
D
E

No. of AFQ-4W 200A

Numbering from 0 to 7

F

F:0 No. AFQYY <= 7 units
F: 1 No. AFQYY == 8

where YY: Range of AFQ 25,
50, 100, 150, 200

Flag indication of 8 AFQ-4W of the