4.3.3.- CONFIGURATION OF PARAMETERS

This menu (

Figure 56

) contains the parameters that have to be configured during

the installation of the active filter. To be modify these parameters, you have to

unlock the password (refer to 4.3.6.- PASSWORD) and have the filter in “STOP

mode.

Figure 56: Parameter configuration screen.

Transformer ratio:

The ratio between the load transformer primary and secondary.

The active filter admits the following transformation ratios: 5/5, 10/5, 15/5, 20/5,

25/5, 30/5, 40/5, 50/5, 60/5, 75/5, 100/5, 125/5, 150/5, 200/5, 250/5, 300/5,

400/5, 500/5, 600/5, 700/5, 750/5, 800/5, 1000/5, 1200/5, 1500/5, 1600/5,

2000/5, 2500/5, 3000/5, 4000/5 and 5000/5.

Minimum current:

The minimum load current to start the active filter. The AFQ-4W will stop when

the load current is below the entered value and will start when it is higher.

Control algorithm:

Control algorithm selection:

1, Frequency mode: Harmonic filtering based on the selection of the

harmonics to be neutralised from the 3rd to the 25th. (Option enabled by

default.)

2, Temporary mode: Harmonic filtering based on the total and instant

neutralisation of the 3rd to 50th harmonics.

When the temporary mode is active, the AFQ-4W resets all the harmonics

selected in “Selective filtering” (Section 4.3.2.2) to completely neutralise

the harmonics.