Active, Filter, Alarm – CIRCUTOR AFQ Series User Manual

Page 93: Status

Advertising
background image

AFQ-4W

Instruction Manual 93

ACTIVE FILTER IN ALARM STATUS

Table 13

shows the messages that might appear on the main screen when the

AFQ-4W is in an alarm status.

ALARM

NTC1 temperature

Description

NTC probe overtemperature.

Corrective

Action

Make sure that the fans or turbines at the top of the cabinet are
operating properly.

NTC2 temperature

Description

NTC probe overheating

Corrective

Action

Make sure that the fans or turbines at the top of the cabinet are
operating properly.

Inductor Temperature

Description

Inductor overtemperature

Corrective

Action

Ensure that the fans at the bottom of the cabinet are operating
properly.

MAX. DC bus voltage.

Description

The voltage on the DC bus capacitors is too high.

Corrective

Action

Check the unit connections and the input voltages.

MAX. Bus positive voltage

Description

The voltage on the DC bus capacitors is too high.

Corrective

Action

Check the unit connections and the input voltages.

MAX. Bus negative voltage

Description

The voltage on the DC bus capacitors is too high.

Corrective

Action

Check the unit connections and the input voltages.

MAX. Current

Description

The AFQ-4W current is too high.

Advertising