Function selection – CIRCUTOR AFQ Series User Manual

Page 51

Advertising
background image

AFQ-4W

Instruction Manual 51

4.3.2.1.- FUNCTION SELECTION

Use this screen (

Figure 53

) to select the functions of the AFQ-4W:

Figure53: Function selection screen.

Harmonic filtering: Current harmonic neutralisation. (This option is enabled by

default.)

Phase balancing: Balancing of the current between phases. (This option is not

enabled by default.)

Reactive compensation: A function that allows the shifting of the cos

Φ to be

compensated. (This option is not enabled by default.)

Function priority Order: The AFQ-4W allows the functions to be prioritised in

the event of filter current saturation by overload. When the “Function priority

order ” function is disabled, priority is given to the current harmonic filtering and

reactive compensation and overload balancing are penalised. If “Function

priority order” is activated, priority is given to current balancing between phases

and reactive current compensation, ahead of harmonic neutralisation. (This

option is not enabled by default.)

Function priority order

P

R

IOR

IT

Y

-

+

OFF

ON

Harmonic filtering

Phase balancing +

reactive compensation

Phase balancing +

reactive compensation

Harmonic filtering

Table 7: Configuration of the order of priorities.

Click on the Main key to open the home screen.

Click on the Back key to return to the work mode screen.

Advertising