CONTA-CLIP SMS-MULTI I/O User Manual

Page 26

Advertising
background image

SMS-MULTI-IO



- 25 -





5.4

5.4

5.4

5.4

Analog input

Analog input

Analog input

Analog inputssss

To use as a current input, lift the lid (see 3.1) and place a 250Ω / 0.1% resistor into the header on Ri:

To use as a voltage input the header must be empty.

5.4.1

5.4.1

5.4.1

5.4.1

Configuration

Configuration

Configuration

Configuration

Configure the following items with the software:

Name, this name must be unique and can not be used with any other input or output.

Default set as AI1 to AI8.

The input source:

0..10V

0..20mA

4..20mA

The unit for the input feedback. E.g. litres (Ltr) or kilograms (kg).

The min. value represents the scaled value for 0V, 0mA or 4mA.

The max. value represents the scaled value for 10V, 20mA.

Lower limit threshold.

Upper limit threshold.

Minimal change (hysteresis).

The Analog Inputs can generate messages with value and unit when:

The upper limit + hysteresis is reached

The lower limit – hysteresis is reached

The status recovers between the upper and lower limit +/- hysteresis


Note:

Note:

Note:

Note: The min./max. and threshold/hysteresis values are limited to 5 digits with a maximum of 2
decimals.

E.g.:

E.g.:

E.g.:

E.g.:
A water tank level is converted to 0..10V. 0V represents 10 litres and 10V represents 100 litres.
If a message should be sent

when the tank reaches a minimum of 20 litres and when during filling

the level of 80 litres is reached, configure the module as follows: