CONTA-CLIP SMS-MULTI I/O User Manual

Page 29

Advertising
background image

SMS-MULTI-IO



- 28 -

5.6

5.6

5.6

5.6

RTD input

RTD input

RTD input

RTD inputssss

To use as RTD input lift the lid (see 3.1) and place a 5.11kΩ / 0.1% resistor into the header on Rt:

Connect the RTD element between ground and the RTD input.

5.6.1

5.6.1

5.6.1

5.6.1

Configuration

Configuration

Configuration

Configuration

Configure the following items with the software:

Name, this name must be unique and can not be used with any other input or output.

Default set as RTD1 to RTD8.

The unit for the input feedback:

°C, degrees Celsius

°F, degrees Fahrenheit

The RTD element:

PT1000

NI1000

PT100

Lower limit threshold.

Upper limit threshold.

Minimal change (hysteresis).

The Analog Inputs can generate messages with value and unit when:

The upper limit + hysteresis is reached

The lower limit – hysteresis is reached

The state recovers between the upper and lower limit +/- hysteresis


Note:

Note:

Note:

Note: The threshold/hysteresis values are limited to 5 digits with a maximum of 2 decimals.