BE1-79A Controls and Indicators

9310200990 Rev J

Style Configuration Switches

Three switches on the left side of the relay cradle are used to configure the BE1-79A for either ACR11A

or ACR11B operation. For simplicity, recloser styles ACR11B, ACR11C, ACR11D, ACR11E, and ACR11F

will be referred to as ACR11B throughout this manual. Figure 2-2 illustrates the location of the style

configuration switches. The BE1-79A is delivered with switches S1, S2, and S3 placed in the “A” position.

Figure 2-2. Style Configuration Switches

Instantaneous Reclose Jumper Switch and RS Contact Switch

Two switches on the right side of the relay cradle select either internal or external jumpering for an

instantaneous first reclosure and for selecting normally-closed or normally-open operation of the RS

contact. Switch S4 is used to select internal or external jumpering and switch S5 is used to select

normally-open or normally-closed operation of the RS contact. Figure 2-3 illustrates the location of

switches S4 and S5. The BE1-79A is delivered with switch S4 placed in the “EXT” position and switch S5

placed in the “NC” position.