BE1-79A Functional Description
3-7
Recloser Operation
Information about the software-controlled features of the recloser is provided in the following paragraphs.
Power-Up
The flow chart of Figure 3-4 describes relay operation following the application of operating power.
Depending on conditions and the reset delay setting, the interval from power application to the resultant
state may be from 0 to 300 seconds.