Timing cams, Fault clearing, Rs contact – Basler Electric BE1-79A User Manual

Page 48: Alarm output, Timing cams -8, Fault clearing -8, Rs contact -8, Alarm output -8

Advertising
background image

5-8

BE1-79A Installation and Configuration

9310200990 Rev J

5. When all of the jumpers are positioned for operation in the desired sensing voltage range, prepare to

place the circuit board back in the relay chassis.

6. Align the circuit board edges with the white guide markings on the relay chassis. Once aligned, slide

the circuit board back into the chassis until the circuit board is seated in its connector. The front of the

circuit board should be flush with the front of the relay chassis. (The LEDs and serial port connector

will protrude past the front of the chassis.)

7. Place the front panel on the front of the relay chassis and align the four screw holes. Secure the front

panel to the relay chassis with the four Phillips screws removed in step 1.

Timing Cams

Double-ended cams on ACR reclosers provide a 10 second reset after a reclosure. Single-ended cams

can be adjusted for any reclose or reset time desired. The single- and double-ended cams of the ACR

reclosers are simulated with the reclose and reset timer settings of the BE1-79A relay. Since the reclose

and reset times for each of the four recloses is independently programmable, the function of the ACR

reclosers can be duplicated.

NOTE

A reclose time delay must be set for a duration that is longer than the

preceding reset time delay. Setting the reset time delay longer than the next

reclose time delay in the reclose sequence will give undesired results.
Example:

Incorrect

SP-79A1=0,15 SP-79A1=0,7

Correct

SP-79A2=10,15 SP-79A2=10,15

Fault Clearing

The BE1-79A allows the first reclose to be delayed slightly so that faults may de-ionize before a reclosure

is initiated. Faults typically are allowed to de-ionize for approximately 217 milliseconds (13 cycles) for

distribution voltages and 300 milliseconds (18 cycles) for transmission voltages (including breaker-

operating time). The inherent delay of the BE1-79A relay is 22 to 48 milliseconds when set at a time delay

of zero. The reclose timers may be adjusted in increments of 0.1 seconds, which is 6 cycles on a 60-hertz

system.
It is possible to set an ACR recloser for an instantaneous reclose with no voltage applied at terminals 5

and 6. If this unusual application is employed, the user must confirm that voltage is applied to BE1-79A

terminals 5 and 6 when a reclose is desired. Terminals 5 and 6 must be energized for a reclose to be

initiated.
The power holdup circuit of part number 9310200101 relays maintains relay function for a minimum of 40

cycles (667 milliseconds) after nominal operating power is removed. This prevents the relay output

contacts from dropping out too quickly in applications where output C10 is used as an instantaneous trip

enable contact.

RS Contact

A jumper is used in ACR reclosers to configure the RS contact for normally open or normally closed

operation. In the BE1-79A, the RS contact is configured by switch S5. The SP-79RS command allows the

RS contact operate and reset time to be programmed. Refer to Section 4, Communication Commands,

Command Descriptions for a detailed description of the SP-79RS command.

Alarm Output

The SP-ALM command is used to program the alarm output to function as a relay fail output or a

combination relay fail/lockout output. As a relay fail output, the alarm output will close if relay operating

power is lost. The alarm output will also close if the microprocessor detects an abnormal condition such

as:

The BE1-79A is configured for ACR11A operation but recognizes inputs that indicate the relay is

operating in an ACR11B system.

The microprocessor is unsuccessful at storing settings in EEPROM.

Advertising