BE1-79A Installation and Configuration

5-1

SECTION 5 • INSTALLATION AND

CONFIGURATION

General

BE1-79A Reclosing Relays are delivered in sturdy cartons to prevent shipping damage. Upon receipt of a

relay, check the model number against the requisition and packing list for agreement. Inspect for damage

and, if there is evidence of such, file a claim with the carrier and notify the Basler Electric regional sales

office, your sales representative, or the Technical Sales Support department of Basler Electric.
If the relay is not installed immediately, store it in the original shipping carton in a moisture- and dust-free

environment.

Mounting

Because the BE1-79A is of solid-state design, it does not have to be mounted vertically. Any convenient

mounting angle may be chosen. The BE1-79A is available in an S2 cradle or an S1 cradle with case. The

S2 cradle is intended for installation in an existing S2 case. Overall dimensions for the S1 case are shown

in Figure 5-1. S1 case cutout dimensions are shown in Figure 5-2.

Connections

Incorrect wiring may result in damage to the relay. Be sure to use the correct input power for the power

supply and the correct input voltage for the contact inputs. Connections should be made with a minimum

wire size of 14 AWG. Figure 5-3 illustrates the terminal connections of the S1 case. Figure 5-4 provides a

typical connection diagram for an application using an ACR11A style relay. Figure 5-5 shows typical

connections for an application using an ACR11B style relay.

Application

The intended function of the BE1-79A Reclosing Relay is to duplicate an ACR11 recloser with only minor

variations. To ensure that your BE1-79A relay functions properly, you should consider the adjustments

and settings described in the following paragraphs.

Style Configuration Switches

Switches S1, S2, and S3 must be set properly for your application. All three switches should be placed in

the A (up) position for ACR11A operation. All three switches should be placed in the B (down) position for

ACR11B, ACR11C, ACR11E, and ACR11F operation.

Instantaneous Reclose Jumper Switch

Use the following guidelines when setting Instantaneous Reclose Jumper Switch S4.

For ACR11a operation, switch S4 should be placed in the EXT (down) position.

An ACR relay has a red jumper from terminals 13 to 17 for an instantaneous first reclosure

(SP-79A1 0.0,X.X) is duplicated by placing BE1-79A switch S4 in the INT (up) position.

A delayed first reclosure is achieved when S4 is placed in the EXT (down) position and the external

jumper is removed from terminals 13 and 17.

If an external jumper is left in place at terminals 13 and 17 for an instantaneous first reclosure, S4

should be placed in the EXT (down) position.

Neither an internal nor an external jumper is required at terminals 12 and 13 for a delayed first

reclosure. Switch S4 should be placed in the EXT (down) position for delayed reclosures.

RS Switch

RS switch S5 is used to control the RS contact for normally open or normally closed contact configuration.

Figure 2-2 and 2-3 should be consulted for the location and setting positions of the style and configuration