Be1-79a – Basler Electric BE1-79A User Manual
Page 55
Advertising
9310200990 Rev J
BE1-79A Testing
6-3
6. Place Test switch S1 in the 52b position before 20 seconds elapse and verify that after 30 seconds,
Reclose indicator L2 lights for three seconds.
7. Place Test switch S1 in the 52a position and verify that after 40 seconds, the front panel Reset LED
and Reset indicator L1 light.
Figure 6-1. Test Connections for ACR11A Style Relays
L3
L2
L1
Reclose
Lockout
Reset
S1
52A
52A
52B
52B
120 Vac
A
B
C
Auxiliary Contact - Closed in Reset
RS Contact - Closes, opens at time set by user
Instantaneous First Reclose
Contact closes when terminal 7 is energized
Delayed First Reclose
External Jumpers
BE1-79A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
B
C
A
D2588-08
08-01-05
(Front view. For making connections
with GE XLA test plugs.)
NC
NO