9310200990 Rev J

BE1-79A Testing

6-3

6. Place Test switch S1 in the 52b position before 20 seconds elapse and verify that after 30 seconds,

Reclose indicator L2 lights for three seconds.

7. Place Test switch S1 in the 52a position and verify that after 40 seconds, the front panel Reset LED

and Reset indicator L1 light.

Figure 6-1. Test Connections for ACR11A Style Relays

L3

L2

L1

Reclose

Lockout

Reset

S1

52A

52A

52B

52B

120 Vac

A

B

C

Auxiliary Contact - Closed in Reset

RS Contact - Closes, opens at time set by user

Instantaneous First Reclose

Contact closes when terminal 7 is energized

Delayed First Reclose

External Jumpers

BE1-79A

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

B

C

A

D2588-08

08-01-05

(Front view. For making connections

with GE XLA test plugs.)

NC

NO

S5