Rs contact example for transformer ltc blocking, Sp-79ars mode selection, Sp-79ars remove time selection – Basler Electric BE1-79A User Manual

Page 64

Advertising
background image

A-4

BE1-79A RS Contact Application

9310200990 Rev J

From Table A-1, for mode E settings, an NO RS contact (S5 = NO, mode = E) will be open during BE1-

79A power-off and will be energized and closed when the BE1-79A relay is powered on and in Reset

position. The NO contact will remain closed until the reclose cycle begins. At that time, the NO contact will

continue to remain closed until the RS Apply time is reached. The NO contact will then open and remain

open until the RS contact Remove time is reached. (If relay power is lost during this time, the NO contact

will remain open.)
When the Remove time is reached or the BE1-79A resets, the NO contact will again close and remain

closed until the next reclose cycle begins from the Reset position.

RS Contact Example for Transformer LTC Blocking

SP-79ARS Mode Selection

If using the de-energized mode (mode = D), be aware that the RS contact will revert to the de-energized

state during loss of BE1-79A operating power. Therefore, if power is lost during the reclose cycle, the NO

RS contact (S5 = NC) being held open to block the LTC will change state and remove the LTC blocking

while the relay is without power. If a reliable dc power source to terminals 5 and 6 is available, it will

prevent this from occurring.
If using the Energized mode (mode = E) and the normally open RS contact (S5 = NO), it will revert to the

de-energized state during loss of BE1-79A operating power. If operating power is lost during the reclose

cycle, the NO RS contact being held open to block the LTC will remain open and continue the block. If the

relay power to terminals 5 and 6 is lost at any other time (during breaker maintenance, a common dc

power source may be turned off), the RS contact will change state and block the LTC, which may be

undesirable under these circumstances. Awareness of this condition will enable the user to take the

necessary steps to prevent the condition from occurring.

SP-79ARS Remove Time Selection

The RS contact Remove time, when used for LTC blocking, should be long enough to allow a complete

reclose cycle to occur but shorter than the final closure’s reset time and before lockout time is reached.

This ensures that the RS contact is blocking LTC operation during the reclose sequence but is reset to its

normal condition before the next reclose cycle begins. The LTC will then be functioning normally even

when the breaker has operated to the lockout condition.

RS Contact Example for Blocking Instantaneous Overcurrent Tripping

The BE1-79A has the following settings with switch S5 set for NC:
SP-79A1=0,10

SP-79A2=15,25

SP-79A3=45,55

SP-79A4=0,0

SP-79ALO=60,65

SP-79ARS=D,5,58

SP-ALM=2
With the NC (in de-energized mode) BE1-79A RS contact wired in series with an instantaneous over-

current (50) device trip circuit, it will open or block tripping of a circuit breaker by the 50 element five

seconds after the first trip of the breaker. The BE1-79A is programmed to close the breaker instantly for

its firs close (SP-79A1=0,10). If the breaker trips a second time before 10 seconds have elapsed, the

BE1-79A RS contact will open at the Apply time setting of five seconds and remain open until the Remove

time of 58 seconds from the first trip is reached. This will permit the 50 element to be in service when the

breaker is closed after lockout.
If the breaker successfully closes on any of the three programmed close times of up to 45 seconds from

the first trip and resets, then the Remove time also will be reset. Resetting the Remove time will restore

the RS contact to its original NC position and restore the 50 element tripping for the next fault occurrence

and trip-close sequence of the circuit breaker.
If the 50 element is to remain blocked when the BE1-79A is in lockout, then the RS contact Remove time

should be set for 65 seconds also (SP-79ARS=D,5,65).

Advertising