BE1-79A RS Contact Application

A-1

APPENDIX A • RS CONTACT APPLICATION

Introduction

The functionality of the RS contact in the BE1-79A relay emulates that of an ACR reclosing relay. The RS

contact can be applied to disable the instantaneous trip circuit of protection relays after any close attempt,

typically leaving only time overcurrent protection in service. It can also be used to block transformer load

tap changer (LTC) changes during a reclosing sequence. For transmission line applications, it has been

used to permit operation of other automatic devices such as motor operated switches in line sectionalizing

operations.

RS Contact Output State

To illustrate RS contact operation, Table A-1 lists the possible setting combinations for RS Contact switch

S5 (NO or NC) and the SP-79ARS command mode (D or E). Switch S5 can be selected as normally open

or normally closed to simulate the jumper-selectable RS contact in an ACR relay. Independent of the SP-

79ARS command mode, the S5 NO/NC selection assigns the state of the RS contact when the relay

power supply is de-energized.

Table A-1. RS Contact Operation Table

SP-79ARS

Command

Parameters

S5

Position

RS Contact State When:

BE1-79A

Power Off

BE1-79A

Reset

Applied

Removed

D,0,145

NC

Closed

Closed

Opens as soon as 52b makes

Closes at 145 s

D,2.5,145

NC

Closed

Closed

Opens at 2.5 s

Closes at 145 s

D,0,145

NO

Open

Open

Closes as soon as 52b makes

Opens at 145 s

D,2.5,145

NO

Open

Open

Closes at 2.5 s

Opens at 145 s

E,0,145

NC

Closed

Open

Closes as soon as 52b makes

Opens at 145 s

E,2.5,145

NC

Closed

Open

Closes at 2.5 s

Opens at 145 s

E,0,145

NO

Open

Closed

Opens as soon as 52b makes

Closes at 145 s

E,2.5,145

NO

Open

Closed

Opens at 2.5 s

Closes at 145 s

SP-79ARS command syntax is SP-79ARS[=<mode>,<apply time>,<remove time>]. Mode D indicates that

the RS element is de-energized or “dropped out” when power is applied to BE1-79A terminals 5 and 6.

Mode E indicates that the RS element is energized or picked up when power is applied to BE1-79A

terminals 5 and 6.

Table A-1 Notes

In Applied mode, the RS contact functions opposite of the way it does in Removed mode and BE1-79A

Power Off mode.
When the ac or dc operating power applied to terminals 5 and 6 is interrupted during a reclose sequence,

the RS contact returns to the BE1-79A Power Off state until operating power is restored and the reclosing

sequence is resumed.

The mode of the RS contact offers the ability to invert the relay logic. In D (de-energized) mode, the

position of the RS contact will follow the classic definition of relay logic:

If RS logic is 0, the RS relay coil is de-energized.

If RS logic is 1, the RS relay coil is energized.

In E (energized) mode, the relay logic is inverted and the RS coil is normally energized and then de-

energized when the RS logic goes to 1. The effect is:

If RS logic is 0, the RS relay coil is energized.

If RS logic is 1, the RS relay coil is de-energized.

Note that if E logic is selected and the relay RS logic is 0, the RS coil will be energized and holding the

output contact against its internal spring. However, if the relay loses power at this point, the RS contact

will change state to the open/closed position dictated by RS Contact switch S5. Table A-1 is based on

these explanations and will be referred to throughout the remainder of this appendix.