Decs metering screen – Basler Electric IDP-800 User Manual

Page 27

Advertising
background image

9437600990 Rev F

21

DECS Metering Screen

Access the DECS Metering screen (Figure 23) by pressing the Metering button of the Main View screen.
The DECS Metering screen displays digital metering values for the generator or motor, bus, and exciter
field as well as the excitation setpoint position and control values.

Figure 23. DECS Metering Screen

Analog Metering

Pressing the Analog Meter button accesses the analog representations of the digital values displayed on
the DECS Metering screen. Analog metering values are divided among three screens accessed through
buttons labeled Generator Values, Generator Power, and Exciter Values. Each parameter is represented
by an analog meter along with the digital version of the metered value.

Trending

Access to the Trending and Capability Curve screens is also provided through the Trending and
Capability buttons on the DECS Metering screen.

The Trending screen (Figure 24) is accessed by pressing the Trending button of the DECS Metering
screen. Several system parameters can be selected and monitored over time in an amplitude-versus-time
window. Buttons on the Trending screen enable selection of the parameters to be monitored. Available
parameters include generator voltage (Vgen), apparent power (kVA), true power (kW), reactive power
(kvar), field voltage (Vexc), and field current (Iexc). Parameters are plotted in a color that matches the
color of the parameter buttons. Pressing the History button displays additional controls and a display for
manipulating the cursor position within a data plot. Pressing the USB button accesses the Memory
Transfer screen where the data from a trending plot can be transferred to USB memory device. Storage
of trending information requires the installation of a compact flash memory card.

IDP-800

IDP-800-B Operation