9437600990 Rev F

45

Register

Data Description

Access

Data Format

up, b12= gen. below 10Hz, b13=unassigned, b14=exciter diode
open, b15=exciter diode shorted.

47300-01

The active operating setpoint expressed as a percent of its
present adjustment range.

R-

R32_23

47302

The state of some contact inputs: b0 = 52JK, b1 = 52LM, b2 =
Automatic transfer, b3 = External Tracking Enable

R-

UI16

47303

Annunciation status bit flags (0=clear, 1=annunciation present):
b0=field overvoltage, b1=field overcurrent, b2=gen. undervoltage,
b3=gen. overvoltage, b4=underfrequency, b5=in OEL, b6=in UEL,
b7=in FCR mode, b8=loss of sensing voltage, b9=setpoint at
lower limit, b10=setpoint at upper limit, b11=gen. failed to build
up, b12= gen. below 10Hz, b13=unassigned, b14=exciter diode
open, b15=exciter diode shorted..

R-

UI16

47306

Protection status bit flags (0 = clear, 1 = condition present)
b0 = loss of field, b1 = in SCL, b2 – b15 are unassigned

R-

UI16

47307

Annunciation status bit flags (0 = clear, 1 = condition present)
b0 = loss of field, b1 = in SCL, b2 – b15 are unassigned

R-

UI16

DECS-200, DECS-250, and DECS-250N Operating Mode Information Category C5

Category CT holding register assignments and descriptions are listed in Table 4.

Table 4. DECS-200/DECS-250/DECS-250N Operating Mode Information Category C5

Register

Data Description

Access

Data Format

47571

Operating mode: 0 = Off / 1 = PF Control / 2 = var Control

R-

UI16

47572

Unit mode status: 0 = Stop / 1 = Start

R-

UI16

47573

Control mode status: 1 = FCR / 2 = AVR

R-

UI16

DECS-200, DECS-250, and DECS-250N Setpoints Information Category C6

Category C6 holding register assignments and descriptions are listed in Table 5.

Table 5. DECS-200/DECS-250/DECS-250N Setpoints Information Category C6

Register

Data Description

Access

Data Format

47621-22

FCR (field current regulator) mode setpoint; adjustment range is
determined by registers (47699-700) and (47707-08)

RW

R32_23

47623-24

AVR (automatic voltage regulator) mode setpoint; adjustment
range is determined by registers (47701-02) and (47709-10)

RW

R32_23

47625-26

Var mode setpoint (in kvar); adjustment range is determined by
registers (47703-04) and (47711-12)

RW

R32_23

47627-28

PF mode setpoint; adjustment range is determined by registers
(47705-06) and (47713-14)

RW

R32_23

47699-700

FCR minimum setpoint (in amps) = % of nominal x rated field
current:(regs. 47655-56) x (regs. 47529-30) / 100

R-

R32_23

47701-02

AVR minimum setpoint (in volts) = % of nominal x rated gen.
voltage:(regs. 47657-58) x (regs. 47525-26) / 100

R-

R32_23

47703-04

Var minimum setpoint (in kvar) = % of nominal x rated generator
VA:(regs. 47659-60) x rated VA / 100

R-

R32_23

47705-06

PF minimum setpoint = registers 47661-62

R-

R32_23

47707-08

FCR maximum setpoint (in amps) = % of nominal x rated field
current:(regs. 47663-64) x (regs. 47529-30) / 100

R-

R32_23

47709-10

AVR maximum setpoint (in volts) = % of nominal x rated gen.
Voltage:(regs. 47665-66) x (regs. 47525-26) / 100

R-

R32_23

IDP-800

Modbus™ Communication