Decs-200, decs-250, and decs-250n register tables – Basler Electric IDP-800 User Manual

Page 50

Advertising
background image

44

9437600990 Rev F

Register

Data Description

Access

Data Format

47727

Virtual toggle switch for changing control mode from comm.
Port between AVR and FCR:
0 = no change / 1 = change state.
Holding register 47573 contains Control mode status.

W-

UI16

47728

Switch for changing operating mode via comm. port to one of
three modes.
0=OFF / 1=PF / 2=var.
Holding register 47571 contains Operating mode status.
To change the operating mode in the AVR, it is necessary to
pass the register 47729 at 1

W-

UI16

47729

Load new operation mode to the AVR
0= No change ; 1=change

W-

UI16

47730

Raise input enable status from comm. port:
0 = Off / 1 = On

W-

UI16

47731

Lower input enable status from comm. port:
0 = Off / 1 = On

W-

UI16

DECS-200, DECS-250, and DECS-250N Register Tables

Three categories of DECS-200, DECS-250, and DECS-250N information can be accessed through the
IDP-800 using the Modbus communication protocol: C2 (metering), C5 (operating modes), and C6
(setpoints).

DECS-200, DECS-250, and DECS-250N Metering Information Category C2

Category C2 holding register assignments and descriptions are listed in Table 3.

Table 3. DECS-200/DECS-250/DECS-250N Metering Information Category C2

Register

Data Description

Access

Data Format

47257-58

Average of the 3 rms line-to-line voltages

R-

R32_23

47259-60

Phase B generator current in amps

R-

R32_23

47261-62

Generator apparent power in kVA

R-

R32_23

47263-64

Generator real power in kW

R-

R32_23

47265-66

Generator reactive power in kvar

R-

R32_23

47267-68

Power factor

R-

R32_23

47269-70

Generator frequency in hertz

R-

R32_23

47271-72

Bus frequency in Hz

R-

R32_23

47273-74

RMS bus voltage in volts

R-

R32_23

47275-76

Field voltage in volts

R-

R32_23

47277-78

Field current in amps

R-

R32_23

47283-84

Auxiliary input in volts (PSS input)

R-

R32_23

47287-88

Null balance (tracking error) in percent

R-

R32_23

47295

Status of the Front panel LEDs (bit flags, where 0=off, 1=on for all
LEDs except Null Balance and Internal Tracking which are
reversed): b0=Null Balance, b1=Tracking, b2=Pre-position,
b3=Upper Limit, b4=Lower Limit, b5=Edit, b6-b15=unassigned

R-

UI16

47296

Voltage matching status: 0=off / 1=on

R-

UI16

47297

Protection status bit flags (0=clear, 1=condition present):
b0=field overvoltage, b1=field overcurrent, b2=gen. Undervoltage,
b3=gen. overvoltage, b4=underfrequency, b5=in OEL, b6=in UEL,
b7=in FCR mode, b8=loss of sensing voltage, b9=setpoint at
lower limit, b10=setpoint at upper limit, b11=gen. failed to build

R-

UI16

Modbus™ Communication

IDP-800