Figure 26. UEL Curve Selection Screen

DECS Analog Metering

Analog representations of the digital metering values shown on the DECS Metering screen (Figure 23)
can be accessed by pressing the Analog Meter button. Pressing this button accesses the Generator
Values or Motor Values screen which displays analog representations of the generator/motor voltage,
current, frequency, and power factor. Each analog representation displays the digital equivalent in the
upper, left corner. The remaining analog metering values are divided between two screens: the Generator
Power or Motor Power screen and the Exciter values screen. The Generator Power or Motor Power
screen is accessed from the Generator/Motor Values screen or Exciter Values screen by pressing the
Generator Power or Motor Power button. This screen displays analog representations of the
generator/motor active power, reactive power, and apparent power. The Exciter Values screen is
accessed from the Generator/Motor Values screen or Generator/Motor Power screen by pressing the
Exciter Values button. This screen displays analog representations of the excitation voltage and current.
A Digital Meter button, on each analog metering screen, can be pressed to return to the DECS (digital)
Metering screen.

DECS Control

Access to the DECS Control screen is possible only when logged in with the appropriate password. When
logged in, a Control button on the Main View screen provides access to the DECS Control screen
illustrated in Figure 27. This screen has two buttons: a Setpoint Control button and a Regulation Control
button.

IDP-800

IDP-800-B Operation