Register

Data Description

Access

Data Format

47306

Protection status bit flags (0 = clear, 1 = condition present):
b0=failed to build up, b1=build-up activated, b2= power input
failure, b3 = crowbar activated, b4 - b15 are unassigned.

R-

UI16

47307

Annunciation status bit flags (0 = clear, 1 = condition present)
b0=failed to build up, b1=build-up activated, b2= power input
failure, b3 = crowbar activated, b4– b15 are unassigned.

R-

UI16

DECS-200N Operating Mode Information Category C5

Category C5 holding register assignments and descriptions are listed in Table 7.

Table 7. DECS-200N Operating Mode Information Category C5

Register

Data Description

Access

Data Format

47571

Operating mode ( 0=OFF/ 1=PF/ 2=VAR)

R

UI16

47572

Unit mode status (1=START, 0=STOP)

R

UI16

47573

Control mode status (1=FCR, 2=AVR)

R

UI16

DECS-200N Setpoints Information Category C6

Category C6 holding register assignments and descriptions are listed in Table 8.

Table 8. DECS-200N Setpoints Information Category C6

Register

Data Description

Access

Data Format

47621-22

FCR mode (field current) setpoint

RW

R32_23

47623-24

AVR mode (generator voltage) setpoint

RW

R32_23

47625-26

Var mode setpoint in kvar

RW

R32_23

47627-28

PF mode setpoint

RW

R32_23

47699-700

FCR minimum setpoint

R-

R32_23

47701-02

AVR minimum setpoint

R-

R32_23

47703-04

Var minimum setpoint in kvar

R-

R32_23

47705-06

PF minimum setpoint

R-

R32_23

47707-08

FCR maximum setpoint

R-

R32_23

47709-10

AVR maximum setpoint

R-

R32_23

47711-12

Var maximum setpoint in kvar

R-

R32_23

47713-14

PF maximum setpoint

R-

R32_23


IDP-800

Modbus™ Communication