2 ups functions, 1 beckhoff ups configuration dialog – BECKHOFF CX2100­09x4 User Manual

Page 46

Advertising
background image

Commissioning

5.2

UPS functions

5.2.1

BECKHOFF UPS Configuration dialog

5.2.1.1

Beckhoff UPS configuration dialog

Following installation under Win2K/XP/XPe/WES 7 the UPS configuration dialog will be found as an
additional tab under Control Panel ­> Power Options.

Under NT4.0 UPS configuration dialog can be called via the shortcut under Control Panel ­> BECKHOFF
UPS Configuration
.

Under Windows Vista or Windows 7 you can reach the UPS configuration dialog via the link in the Start
menu: Start­>All Programs­>BECKHOFF­>UPS Software Components­>UPS Configuration

The UPS devices that are connected to the serial interface can in fact be fully configured via the standard
dialog under Control Panel ­> Power Options ­> UPS. The setting facilities are adequate for an office PC, but
it is not always possible to achieve an optimum configuration through this dialog for an Industrial PC with a
UPS. An additional dialog is therefore made available under Control Panel ­> Power OptionsBECKHOFF
UPS Configuration

This dialog can be used, for instance, to make device­specific settings on the CP903x card, or to carry out a
firmware update for the P24Vxxxx UPS. The supplementary dialog also allows the maximum "time on
battery"
 to be set to < 2 minutes, and for the delay time for switching off the UPS to be configured.

The UPS configuration settings can be made solely by a user with administrator rights. The corresponding
dialogs are disabled for other users.

CX2100­09x4

46

Version 1.1

Advertising