Commissioning

Name

Type

Description

Default value

BatteryCapacity

REG_DWORD

Remaining UPS battery capacity in percent.
This element can adopt a value between 0
and 100 (the value displayed is rounded up).

0

BatteryStatus

REG_DWORD

Current status of the UPS battery. This
element can adopt the following values:

• 0 := the battery status is unknown;

• 1 := the battery status is OK;

• 2 := the battery must be exchanged;

0

CommStatus

REG_DWORD

Status of communication with the UPS. This
element can adopt the following values:

• 0 := the communication with the UPS

has an unknown status;

• 1 := the communication with the UPS is

OK;

• 2 := the communication with the UPS

has been interrupted.

0

FirmwareRev

REG_SZ

Returns the UPS firmware version number as
a string.

""

SerialNumber

REG_SZ

Returns the UPS serial number as a string.

""

TotalUPSRuntime

REG_DWORD

The remaining UPS battery time in minutes.

0

UtilityPowerStatus

REG_DWORD

Returns the status of the power supply. This
element can adopt the following values:

• 0 := the status of the power supply is

unknown;

• 1 := the power supply is OK;

• 2 := a power failure has been detected;

0

TcPowerFailCnt

REG_DWORD

Power failure counter. The counter increments
every time a power failure is detected.

0

BatteryReplaceDate REG_SZ

Date of the last battery change. The date can
be set with a command in the Beckhoff UPS
Configuration dialog ­> Device
Configuration…. Implemented in the UPS
software v3.0.0.8
 and higher.

""

TcChargeFlags

REG_DWORD

Battery charge and status flags. This element
can adopt one or more values (bits) combined:

• 0 := unknown status (all bits are zero)

• 1 := charge status "High" (bit 0 is set);

• 2 := charge status "Low" (bit 1 is set);

• 4 := charge status "Critical" (bit 2 is set);

• 8 := charge status "Charging" (bit 3 is

set);

• Bit 4 ­ 6 reserved;

• 128 := No battery connected/found (bit 7

is set);

• 256 := UPS fan error (bit 8 is set);

• Bit 9 is reserved;

• 1024 := Battery change interval service

has expired (bit 10 is set). Implemented
in the UPS software v3.0.0.8 and
higher.

• Bit 11 ­ 31 reserved;

0