BECKHOFF CX2100­09x4 User Manual

Page 53

Advertising
background image

Commissioning

Setting/command

Area

Default value

Description

UPS soft­

ware ver­

sion

Activate all notifications

Deactivated

or activated

Deactivated

(checkbox not

checked)

This option can be used to instruct
the operating system to send
messages to the user in case of
Power failure.

Seconds between the power
failure and the first notification

0..120 [s]

5

The delay after which the first
"power fail" message will be sent.

v2.0.0.15

Seconds between further
power failure notifications

0..300 [s]

20

The time that elapses before
additional messages are sent to the
user.

v2.0.0.15

Critical alarm

­

­

The alarm is triggered once the
battery voltage has fallen to a
certain level or once battery
operation has exceeded a certain
time limit.

­

Minutes remaining for battery
operation before critical alarm:

0..720 [min]

2

If you have selected this option, the
UPS service will initiate the critical
alarm after the set time and will
shut down the PC. The critical
alarm may, however, be issued
earlier if the battery capacity is
exhausted. If the value is set to 0,
the PC will be shut down
immediately in the event of a power
failure, and the OS shutdown can
no longer be stopped.

­

On alarm, execute the
following program (task)*

Deactivated

or activated

Deactivated

(checkbox not

checked)

With this option an application can
be executed on alarm, but before
the actual shutdown (Task
Scheduler shutdown task). The
Task Scheduler tasks found are
displayed in the list below after
selecting this option. Subsequently,
a task must be selected from the
list. The default task with the name
"UPS System Shutdown Program"
is automatically selected if it exists
and if no other task has been
configured beforehand.

­

Combo box (task list)

Task Sched­

uler tasks

"UPS System

Shutdown

Program"

Please do not forget to set the user
name and his password during the
configuration of the shutdown task.
The shutdown task is managed by
the Windows Task Scheduler and
can only be executed in a certain
user context. The configured user
may require special access rights
to the system, drives, etc. If the
configured user name/password
corresponds to the logged­in user,
the shutdown task is interactively
executed (visible in the
foreground). "NT AUTHORITY
\SYSTEM" can be also entered as
the system user account (system
account, a password is not
necessary in this case). The
system user account has full
access to the local computer, but

v3.0.0.10

CX2100­09x4

53

Version 1.1