BECKHOFF CX2100­09x4 User Manual

Page 51

Advertising
background image

Commissioning

Setting/command

Area

Default value

Description

Battery type

0..99

1

Only specific for the Beckhoff P24Vxxxx UPS
from firmware version >= 24.1.I and required,
for example, in order to calculate the remaining
battery capacity in battery mode.

Nominal battery
capacity

0..99900 [mAh]

3400

Only specific for the Beckhoff P24Vxxxx UPS
from firmware version >= 24.1.I and required,
for example, in order to calculate the remaining
battery capacity in battery mode.

Battery internal
resistance

0 ­ 999 [mOhm]

120

Only specific for the Beckhoff P24Vxxxx UPS
from firmware version >= 24.1.I and required,
for example, in order to calculate the remaining
battery capacity in battery mode.

Battery change
interval service

0 ­ 480

[months]

60 (5 years)
and checkbox
not checked

Only for the Beckhoff P24Vxxxx UPS from UPS
software v3.0.0.8
 or higher. An interval service
can be configured for this on whose expiry battery
change warnings are written into the Windows
event log. Use the checkbox to activate or
deactivate the function. The number of months
before the first warning must additionally be
configured in the Edit field. The function is only
available if the date of the last battery change and
the Windows system time (in the taskbar) have
also been correctly set/configured. The UPS
service compares the date of the last battery
change + interval service with the system date. If
the system date is exceeded, a warning is written
into the event log. The warning does not provide
any information about the actual battery state and
can only be used as a reminder to check the
battery state/age.

Last service: 01.01.11*

­

­

Displays the date of the last battery change (last
service was on January 1, 2011).

Next service:
01.01.16*

­

­

Shows the prospective date of the next battery
change (next service is due on January 1, 2016).

Reset interval service
message…

­

­

Only for the Beckhoff P24Vxxxx and some APC
devices. Updates the date of the last battery
change and resets the interval service message.
The date is stored in the UPS's EEPROM, and
can be examined in the UPS information [

}

 49]

dialog.

set to: 25.05.12*

­

­

Displays the date which is suggested when
resetting the service message. The last battery
change/service is updated to this date (the current
date is May 25, 2012).

Firmware update...

­

­

Only for the Beckhoff P24Vxxxx from firmware
version: >= 21.1.I.
 Starts a firmware update. Only
starts a firmware update if you actually have a
suitable new firmware file.

Self­test

­

­

Only for the Beckhoff P24Vxxxx and some APC
devices. Executes a self­test and displays the
result:

• "OK" ­ Test successful, the battery is OK;

• "BT" failed due to insufficient battery

capacity or no battery is present\connected
at all;

• "NG" ­ Failed as a result of overload;

• "NA" ­ Test function does not exist;

CX2100­09x4

51

Version 1.1

Advertising