BECKHOFF CX2100­09x4 User Manual

Page 80

Advertising
background image

Error handling and diagnostics

LEDs for K­bus diagnostics

Error code

Error code argu­
ment

Description

Remedy

Persistent,
continuous
flashing

EMC problems

• Check power supply for undervoltage or

overvoltage peaks

• Implement EMC measures

• If a K­Bus error is present, it can be

localized by a restart of the power supply
(by switching it off and then on again)

1 pulse

0

EEPROM checksum
error

Revert to the manufacturer’s setting

1

Code buffer overflow

Insert fewer Bus Terminals. Too many entries in
the table for the programmed configuration

2

Unknown data type

Software update required for the power supply

2 pulses

0

Programmed
configuration has an
incorrect table entry

Check programmed configuration for
correctness

n (n > 0)

Table comparison
(Bus Terminal n)

Incorrect table entry

3 pulses

0

K­bus command error

• No Bus Terminal inserted

• One of the Bus Terminals is defective;

halve the number of Bus Terminals
attached and check whether the error is
still present with the remaining Bus
Terminals. Repeat until the defective Bus
Terminal is located.

4 pulses

0

K­Bus data error,
break behind the
power supply

Check whether the n+1 Bus Terminal is correctly
connected; replace if necessary.

n

Break behind Bus
Terminal n

Check whether the Bus End Terminal 9010 is
connected.

5 pulses

n

K­bus error in register
communication with
Bus Terminal n

Exchange the n

th

 bus terminal

7 pulses

0

Process data lengths
of the set and actual
configurations do not
correspond

Check configuration and terminals for
consistency

9 pulses

0

Checksum error in
Flash program

Revert to the manufacturer’s setting

n (n>0)

Bus Terminal n is not
consistent with the
configuration that
existed when the boot
project was created

Revert to the manufacturer's setting which will
clear the boot project.

14 pulses

n

n

th

 Bus Terminal has

the wrong format

Start the power supply again, and if the error
occurs again then exchange the Bus Terminal.

15 pulses

n

Number of Bus
Terminals is no longer
correct

Start the power supply up again.

16 pulses

n

Length of the K­Bus
data is no longer
correct

Start the power supply up again.

CX2100­09x4

80

Version 1.1

Advertising