Shield Patch Cable

Note: Before applying power to the grounded switch, you must use a volt meter to verify there is

no voltage difference between the power supply’s negative output terminal and the switch chassis

grounding point. If the use of shielded cables is required, it is generally recommended to only

connect the shield at one end to prevent ground loops and interfere with low level signals (i.e.

thermocouples, RTD, etc.). Cat5e cables manufactured to EIA-568A or 568B specifications are

required for use with switches.

In the event all Cat5e patch cable distances are short(i.e. all Ethernet devices are located the same

local cabinet and/or referenced to the same earth ground), it is permissible to use fully shielded

cables terminated to chassis ground at both ends in systems void of low level analog signals.