3.10 REAR EXIT HORIZONTAL TERMINATION

For vent configurations requiring more than two 90° elbows, the following formulas apply:

Formula 1: H

T

< V

T

Formula 2: H

T

+ V

T

< 40 feet

Example:
V

1

= 9 FT

V

2

= 6 FT

V

T

= V

1

+ V

2

= 9 + 6 = 15 FT

H

1

= 3 FT

H

2

= 2 FT

H

3

= 1.5 FT

H

R

= H

1

+ H

2

+ H

3

= 3 + 2 + 1.5 = 6.5 FT

H

O

= .03 (four 90° elbows - 90°) = .03 (360° - 90°) = 8.1 FT

H

T

= H

R

+ H

O

= 6.5 + 8.1 = 14.6 FT

H

T

+ V

T

= 14.6 + 15 = 29.6 FT

Formula 1:

H

T

< V

T

14.6 < 15

Formula 2:

H

T

+ V

T

< 40 FT

29.6 < 40

Since both formulas are met, this vent configuration is acceptable.

0

2.5

5

7.5

10

12.5

15

40

10

20

30

17.5

20

1.6

1.6

38.3

90°

V

1

V

2

H

1

H

2

90°

90°

90°

H

3

Simple venting configuration

(only two 90° elbows)

See graph to determine the required vertical rise V

T

for the required

horizontal run H

T

.

REQUIRED

VERTICAL

RISE IN

FEET V

T

HORIZONTAL VENT RUN PLUS OFFSET IN FEET H

T

The shaded area within the lines represents acceptable values for H

T

and H

T

(H

T

) < (V

T

)

16.3