5.8.5 ADDING VENT SECTIONS

Add chimney sections, according to the manufacturers installation instructions. The chimney must extend at
least, 3 feet above its point of contact with the roof and at least 2 feet higher than any wall, roof, building or
obstacle within 10 feet horizontally.

59.1A

3 FT

MIN

3 FT

MIN

3 FT

MIN

3 FT

MIN

10 FT OR

MORE

LESS THAN

10 FT

FLAT ROOF

WALL

2 FT

MIN

10 FT TO

NEAREST

ROOFLINE

RIDGE

LESS THAN

10 FEET

2 FT MIN

2 FT

MIN