27

W415-0791 / C / 04.18.12

5.2.2 VERTICAL INSTALLATION

This application occurs when venting through a roof. Installation kits for

various roof pitches are available from your authorized dealer / distributor. See

accessories to order specifi c kits required.

A.

Determine the air terminal location, cut and frame a square opening as

illustrated in the ceiling and the roof to provide the minimum 1“ clearance

between the vent pipe and any combustible material. Try to center the vent

pipe location midway between two joists to prevent having to cut them. Use

a plumb bob to line up the center of the openings. A vent pipe shield will

prevent any materials such as insulation, from fi lling up the 1” air space

around the pipe. Nail headers between the joist for extra support.

B.

Apply a bead of caulking (not supplied) to the framework or to the Wolf

Steel vent pipe shield plate or equivalent (in the case of a fi nished

ceiling), and secure over the opening in the ceiling. A fi restop must be

placed on the bottom of each framed opening in a roof or ceiling that the

venting system passes through. Apply a bead of caulking all around and place a

fi restop spacer over the vent shield to restrict cold air from being drawn into the

room or around the fi replace. Ensure that both spacer and shield maintain the

required clearance to combustibles. Once the vent pipe is installed in its fi nal

position, apply sealant between the pipe and the fi restop assembly.

C.

In the attic, slide the vent pipe collar down to cover up the open end of the shield and

tighten. This will prevent any materials, such as insulation, from fi lling up the 1” air space

around the pipe.

21.1

CAULKING

VENT PIPE

SHIELD

FIRESTOP

UNDERSIDE OF

JOIST

VENT

PIPE

COLLAR

VENT

PIPE

SHIELD