3.11 TOP OR REAR EXIT VERTICAL TERMINATION

Simple venting configurations.

See graph to determine the required vertical rise V

T

for the

required horizontal run H

T

.

REQUIRED

VERTICAL

RISE IN

FEET V

T

HORIZONTAL VENT RUN PLUS OFFSET IN FEET H

T

For vent configurations requiring one or more 90° elbows (top exit) or one or more 90° elbows (rear
exit), the following formulas apply:

Formula 1: H

T

< V

T

Formula 2: H

T

+ V

T

< 40 feet

Example:
V

1

= 5 FT

V

2

= 6 FT

V

3

= 10 FT

V

T

= V

1

+ V

2

+ V

3

= 5 + 6 + 10 = 21 FT

H

1

= 8 FT

H

2

= 2.5 FT

H

R

= H

1

+ H

2

= 8 + 2.5 = 10.5 FT

H

O

= .03 (four 90° elbows - 90°)

= .03 (360° - 90°) = 8.1 FT
H

T

= H

R

+ H

O

= 10.5 + 8.1 = 18.6 FT

H

T

+ V

T

= 18.6 + 21 = 39.6 FT

Formula 1:

H

T

< 3.5 V

T

18.6 < 21

Formula 2:

H

T

+ V

T

< 40 FT

39.6 < 40

Since both formulas are met, this vent configuration is acceptable.