StarPac Intelligent Control System FCD VLENIM0066-05 04/14

24

®

Figure 9: Analog Input Power Jumper Settings

11 RS-485 Communication Configurations

11.1 System Communication Default Configuration

The StarPac 3 has two communication ports (Com A and Com B) that can be used for RS-485 communications. Refer
to Figure 6 and Table IX for wiring connection instructions.

StarPac 3 units are shipped from the factory ready for installation and operation. Rarely do the units need to be re-
configured prior to operation. Table X lists the factory default communication settings. If these settings are not correct
for the equipment being used, proceed to sections 11.2 to 11.5. The communication settings for each port will need to
be set on the StarPac 3 device through the keypad. Refer to the StarPac 3 User Interface Manual for instructions on how
to change the communication settings on the StarPac 3.

Table X: Factory Default Mode Settings
Description

Setting

Address

1

Parity

Odd

Baud Rate

19,200

Modbus Communication Mode

RTU

RS-485 Termination Resistors

Installed

11.2 Selecting Correct Address Setting

If the StarPac 3 unit is the only StarPac unit on the communication network, the default address (1) is fine.

If multiple units will be operating on the same communication network, each unit must have a unique address. Before
changing the address, the StarTalk XP or StarTalk DTM software can be used to determine what devices are on the line.
(Remember to include devices that may be temporarily off line).

If the default address setting needs to be changed, use the ‘Comm Port’ option in the configuration menu of the local
keypad interface to change the settings.

11.3 Selecting Correct Baud Rate Setting

StarPac 3 units support baud rates of 2400 up to 57,600 baud. However, the Starpac 3 system is shipped from the fac-
tory with COM A set to 19,200 baud and COM B set to 57,600 baud. If the default baud rate setting needs to be changed,
use the ‘Comm Port’ option in the configuration menu of the local keypad interface to change the settings.

JP1 or

JP2

Internal

Loop Power

Setting

JP1 or

JP2

External

Loop Power

Setting